INSULATED WIRES

  • energoprom 

Standard: GOST 6323-79

TU U 31.3-23075526-004:2007 (АППВнг-LS)

Construction

1  Conductor: aluminum (1 class)

2  Core Insulation: PVC

3  Separating layer

 

Application

For electrical equipment at stationary laying in lighting and power circuits, for inflexible installation of electrical equipment, machines, tools and machines for a rated voltage up to 450 V (for networks up to 450/750 V) frequency up to 400 Hz, or dc voltage up to 1000 V. It is intended for pads in steel or plastic ducts, hollow canals of building structures, where  is no frequent bends wires

Technical parameters

  • Rated operational voltage: 450 V
  • Range of cross-sections 2,50 – 6,0 mm²
  • Number of cores: 2, 3
  • Number of wires in the core: 1

 

Nominal

cross-section (mm²)

Maximum outer dimension

(height x width), mm

2х2,5 3,2 х 7,2
2х4,0 3,6 х 8,2
2х6,0 4,1 х 9,1
3х2,5 3,2 х 11,3
3х4,0 3,6 х 12,7
3х6,0 4,1 х 14,2

 

  • Insulation color: on request
  • Оperating temperatures – of  -50 °С to +50 °С
  • Conductor temperature: max. +70 °С
  • Relative humidity: 98% at 35 °C temperature
  • Flame retardant: IEC 60332-1
  • Service life: 15 years

 

Variants of execution

АППВнг-LS: flame retardant – IEC 60332-3 (category A), IEC 61034-2, IEC 60754-1,IEC 60754-2